Product Details
3169 Power Demand Analyzer - FMI
Clamp on Power Demand Analyzer







Download Brochure
Download Brochure
Category:Power Meters & Demand/Quality Analyzers

Description:
Offering a new approach to energy-related measurement


such as energy conservation, ISO14001 testing, equipment diagnosis, and harmonics measurement, to support programs !

Measure up to two 3-phase, 3-wire systems (displays voltage and current for three lines)

Measure up to four single-phase, 2-wire systems

5 A to 5000 A range

Compact and light weight

PC card data storage

Power recording for individual waveforms

Simultaneous recording of demand values and harmonics


Specifications:
Measurement line type Single-phase 2-wire, single-phase 3-wire, three-phase 3-wire, and three-phase 4-wire systems (50/60 Hz)

Number of systems that can be measured (for systems that share the same voltage) Single-phase: 1P2W 4 systems

1P3W 2 systems

Three-phase: 3P3W2M (measures the voltage and current for two lines) 2 systems

3P3W3M (measures the voltage and current for all three lines) 1 system

3P4W (measures the voltage and current for three lines) 1 system

3P4W4I (measures the voltage for three lines and the current for four lines) 1 system


Measurement item Voltage, current, active power, reactive power, apparent power, power factor, integrated value, frequency, harmonics

Measurement range Voltage: 150 V to 600 V, 3 ranges

Current (When using 9660):5 A to 100 A, 4 ranges

Current (When using 9661): 5 A to 500 A, 5 ranges

Current (When using 9669): 100 A to 1 kA, 3 ranges

Current (When using 9667): 500 A / 5 kA, 2 ranges

Current (When using 9694): 0.5 A to 5 A, 3 ranges

Power: 75 W to 9 MW, 108 combination patterns

Basic accuracy 0.2% rdg. 0.1% f.s. + clamp-on sensor accuracy (active power, at 45 to 66 Hz)

Clamp sensor accuracy 9660 (rated for 100 A): 0.3% rdg. 0.02% f.s.

9661 (rated for 500 A): 0.3% rdg. 0.01% f.s.

9669 (rated for 1000 A): 1.0% rdg. 0.01% f.s.

9667 (rated for 5000 A): 2.0% rdg. 1.5 mV

9694 (rated for 5 A): 0.3% rdg. 0.02% f.s.

* f.s. is the sensor's rated primary current value.

Frequency characteristic Fundamental waveforms up to the 50th order 3% f.s. + measurement accuracy (of a 45- to 66-Hz fundamental waveform)

Other functions * PC card (1 slot, PC Card Standerd-compliant Type II, Flash ATA card type),

(9726/ 9727/ 9728 PC card, 128MB to 512MB)

* RS-232C (Printer or PC connected to an RS-232C interface),

* D/A output (3169-21 only, 4 channels),

* External I/O

Display update rate Approx. every 0.5 seconds

(except when using a PC card while accessing the internal memory, or when performing RS-232C communications)

Power supply voltage rating 100 to 240 V AC, 50/60 Hz

Dimensions and weight 210W 160H 60D mm 5 mm (excluding protrusions), 1.2 kg 100 g (3169-20, 3169-21)

Accessories voltage cord set 9438-03 (1) (1 cord each of black, red, yellow, and blue), voltage cord (1), power cord (1), input cord label (1), operating manuals (2) (Advanced edition and Quick Start Guide), CD-R (1) (Advanced edition and RS-232C interface operating manuals), connection cable 9441 (1) (for the 3169-21 only)

Product URL:
http://www.hiokiusa.com/products.php?productid=3169

All form fields are required.

HIOKIUSA.COM | Browse Products | Contact Us | Warranty / Registration | Locate Dealer | HUSA Personnel